Unexplained water use traced to washroom fittings
The meter showed continuous consumption. Testing found a faulty urinal flush control and dripping fixtures, with no concealed pipe leak indicated.

Water leak warning signs
The building had bar supplies, ice machines and multiple toilets. The meter registered about 2.5 litres a minute.
Leak detection methods used
Acoustic readings directed attention to the gents’ toilets. Supplies were isolated in stages, followed by a pressure test.
Where the water leak was found
A failed urinal flush control ran continuously. A bar tap and basin waste also needed attention.
Leak repairs and next steps
The isolated pipework held 3 bar for 45 minutes. ADI recommended repairs to the flush control and leaking fixtures; the case does not record those repairs as completed.
For your facilities team
Unexpected meter movement can come from fittings as well as hidden pipes. Check washroom controls and appliances as part of the investigation.
More commercial leak detection case studies
Petrol garage: 15 litres a minute lost underground
The meter kept moving with every outlet shut. Tracer gas led to a flooded chamber where several mains leaks were repaired.
School: a buried classroom supply capped off
A hissing classroom and saturated ground led to a leaking desk-tap supply. The school chose to cap the branch rather than excavate.